Servo alarms (SV alarm) SV0417
Message – SV0417
ILL DGTL SERVO PARAMETER
Description
A digital serve parameter setting is incorrect. [When bit 4 of diagnosis information No. 203 is 1.]
An illegal parameter was detected by the servo software. Identify the cause with reference to diagnosis information No. 352.
[When bit 4 of diagnosis information No. 203 is 0.] The CNC software detected an illegal parameter. Probable causes are given below (see diagnosis information No. 280).
1) The value specified in parameter No. 2020 as the motor model falls outside the specified range.
2) The motor rotation direction in parameter No. 2022 is not set to a correct value (111 or -111).
3) The speed feedback pulse count per motor rotation in parameter No. 2023 is set to a negative or other incorrect value.
4) The position feedback pulse count per motor rotation in parameter No. 2024 is set to a negative or other
incorrect value.